Add new user to Partizan STD (face-reader) database (Database – Add Person). Fill in the required fields. The Access controller number and Access card number must match, as in the screenshot below
Select the desired operating mode based on your access control requirements. (Config - Analytics and Alarms - Working mode). Then click Save
Select the desired Wiegand mode 26 or 34. (Config - Access control - Wiegand output). Then click Save
Connect the reader to read access cards to the face-reader using the indication on the cable.
Wiegand input:
WGI_D0
WGI_D1
GND
Connect the controller to the face-reader using the indication on the cable.
Wiegand output:
WGO_D0
WGO_D1
GND
Now we need to create a new user in the controller database.
...
For connection The controller to the face-reader, use 5V supply from Partizan output and resistance 330 Ohm. For further information see:
2.4 Extending Module Connection - Instalační manuál 2N Access Unit
- From the manual there are four cables needs as in picture below:
- Don't forget to connect the 5V power also to the Data wires D0 and D1 through 300 Ohm resistors as shown on the picture below:
- Note: user´s ID in face-reader database is a decimal number and in 2N device is displayed in hexadecimal format.
- The access card number should match the user card number in the Partizan STD database